Main Features

  • Wall-mount heavy duty remote paging console with Access level 2 protection to comply with the EN54-16
  • 8 / 16 zone selection buttons
  • All-call button
  • LED test button
  • Power indicator
  • EVAC indicator

 

Share:

CD8-AS 8-Zone Wallmount Mic / Paging Console for IDA8

The CD8-AS consoles use the same architecture as the PPM paging console, with a junction box built into the enclosure for daisy-chaining multiple units (note that only the first console is monitored). The maximum recommended distance between units is 100 m.

As with the PPM paging console, the CD8-AS zone buttons can represent a single zone or group of zones and are easily programmed through the system GUI using "drag and drop" functionality. The Push-To-Talk button can be programmed for PTT or latching operation. System status indicators show the status of all zones and indicators are also provided for Power, Evac and Fault.

The CD8-AS are powered over RS485 via CAT5 (FTP/STP), however if power is not available over RS485 it can be locally powered using a 24 VDC supply.

The CD8-AS  are certified EN54-16 for use on Public Address and Voice Alarm systems.

Product Features

  • Wall-mount heavy duty remote paging console with Access level 2 protection to comply with the EN54-16
  • 8 zone selection buttons
  • All-call button
  • LED test button
  • Power indicator
  • EVAC indicator
  • Status and Fault indicator
  • Compatible with IDA8C System and communicate over a dedicated RS485 for Power, Audio and Data
  • 1 unit is secured on Controller or Secondary unit. 2nd and more on Controller or Secondary are note secured.
  • Max. 32 unit in a system and 10 in Controller-Secondary string
  • EN54-16 certified

Product Specifications

Electrical

  • Power supply: R485 (RJ45/CAT-5)
  • DC / battery power requirements:
  • Voltage: 18 - 26 VDC
  • Power consumption: 120 mA (CD8-AS) / 150 mA (CD16-AS)

Audio

  • Frequency response: -3 dB @ 200 to 8k Hz
  • THD: < 1% @ 1k Hz
  • Output level Max: 6 dBu
  • Noise gate threshold: -84 dBu - 24 dBu
  • Attack time: 8 ms
  • Release time: 100 ms

Monitoring speaker:

  • Impedance: 4 Ohms
  • Output power: 1 W @ 1k Hz
  • Frequency response: -3 dB @ 200 to 12k Hz

System connection:

  • Cable type: CAT-5
  • Length: 100 m

Environmental

  • Operating temperature: -5 ºC ~ +55 ºC
  • Storage temperature: -40 ºC ~ +70 ºC
  • Relative humidity: 15% to 90%
  • Air pressure: 600 to 1100 h Pa
  • IP rating: 30

Heat Dissipation:

  • CD8-AS: 10 BTU/hr
  • CD16-AS: 12 BTU/hr

Mechanical

Dimensions (W x H x D)

  • CD8-AS: 318.6 x 187 x 130 mm

Weight